Outdoor Unit: 80/90 Class SiBE121135
400 Removal Procedure
4
Remove the sound
blanket (outer).
The sound blanket is fragile.
5
Remove the sound
blanket (top inner).
The sound blanket is fragile.
Carefully pass the blanket
through the discharge pipe.
6
Open the sound blanket
(inner) and pass it
through the part of the
mufflers.
The sound blanket is fragile.
Be careful of the notches of
the compressor mount (3
locations).
Step
Procedure Points
(R10436)
Sound blanket (outer)
(R10437)
Sound blanket (top inner)
(R10438)
Mufflers
Sound blanket
(inner)