ESIE15-13C Function Details
Function and Control 53
Cooling
Field setting to control the different value:
Heating
Field setting to control the different value:
Note: If quick cooling/heating function is selected by the customer via remote controller, the unit will
go into quick cooling/heating for 20 minutes, neglecting the selected Te/Tc. After 20 minutes,
the selected Te/Tc setting will receive priority again.
Example:
The customer has to make a choice:
Fix the Te Lower limit and/or the Tc upper limit on a certain value.
OR
Choose the weather dependent Te Lower limit or Tc Upper limit. In this case the customer can
select 2 different outdoor temperatures that will trigger the changeover to a different Te Lower
limit and/or Tc Upper limit.
B
A
Ta
CD
TeS Lower Limit Value
Value Setting
1234
A 2-54- 9 11 13 15
B 2-57-2468
C 2-58- 14 17 20 23
D 2-59- 23 27 31 35
F
E
Ta
GH
TcS Upper Limit Value
Value Setting
1234
E 2-60- 47 48 49 50
F 2-61- 43 44 45 46
G 2-62- 2 5 8 11
H 2-63- 15 18 21 24