Field Setting from Remote Controller ESIE15-13B
78 Field Setting
Graph 1 Target evaporating temperature control in case of factory setting 16(26)-2-01:
Te target acceptable area
Remote controller setting temp.
Te target limited ≤ 20˚C
(to protect the comp.)
Te target limited
≤ Indoor temp. – 11˚
(not to rising wetbulb)
Te (see note) target
acceptable area
Indoor temp. > setting
→ Te target down
Indoor temp. < setting
→ Te target up
Te target limited
≥ Indoor temp. – 25˚
(not to sweat)
Te target limited ≥ 2˚C
(not to freeze)
Freeze protection
(40 min. integrated coil temp. ≤ -1˚C)
Indoor Temp
(˚C DB)