Engineering & Physical Data
Safety Device
MODEL
INDOOR
FFRN25/35CXV1
FFQN25/35CXV1
FFRN50CXV1
FFQN50CXV1
OUTDOOR R(Y)N25CXV1 R(Y)N50CXV1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
LOW PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A
DISC. THERMOSTAT SETTING °C / F N/A
MODEL
INDOOR
FCRN50/60/71EXV1
FCQN50/60/71EXV1
OUTDOOR
R(Y)N50/60CXV1
R(R )(Q)71CXV1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
LOW PRESSURE
SWITCH
TYPE N/A
OPEN kPa / psi N/A
CLOSE kPa / psi N/A
PHASE SEQUENCER N/A
DISC. THERMOSTAT SETTING °C / F N/A
MODEL
INDOOR FCRN100EXV1
OUTDOOR RR90DXV1 RR100DXV1 RR100DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 4140 / 600.46
CLOSE kPa / psi 3310 / 480.07
LOW PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 48 / 6.96
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER N/A YES
DISC. THERMOSTAT SETTING °C / F N/A 130 / 266
MODEL
INDOOR FCRN125EXV1
OUTDOOR RR125DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 4140 / 600.46
CLOSE kPa / psi 3310 / 480.07
LOW PRESSURE
SWITCH
TYPE NC
OPEN kPa / psi 48 / 6.96
CLOSE kPa / psi 152 / 22.05
PHASE SEQUENCER YES
DISC. THERMOSTAT SETTING °C / F 130 / 266