SiBE121135 Troubleshooting with LED
Service Diagnosis 251
Caution: When operation stops suddenly and the operation lamp blinks, it could be "operation mode
conflict".
Check followings;
Are the operation modes all the same for the indoor units connected to multi system outdoor
unit?
If not, set all the indoor units to the same operation mode and confirm that the operation lamp is
not blinking.
Moreover, when the operation mode is automatic, set all the indoor unit operation mode as
"cooling" or "heating" and check again if the operation lamp is normal.
If the lamp stops blinking after the above steps, there is no malfunction.
Operation stops and operation lamp blinks only for indoor unit which different operation mode
is set later. (The first set operation mode has priority.)
Service Monitor The indoor unit has one green LED (LED A) on the control PCB. When the microcomputer
works in order, the LED A blinks.
Floor Standing Type: FVXS Series Floor / Ceiling Suspended Dual Type
Duct Connected Type
BRC1D528 BRC1E52A7, BRC1E52B7
(R11687)
Operation lamp (green)
Operation lamp (green)
(R11688)
Operation lamp (green)
(Q0340)
Operation lamp (red)
(R12851)
Operation lamp (green)
(R17162)
+ The error or warning message also
blinks on the basic screen.
+