EasyManua.ls Logo

Daikin FFQ35B9V1B - Removal of Outdoor Fan; Fan Motor

Daikin FFQ35B9V1B
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Outdoor Unit: 40-75 Class SiBE121135
354 Removal Procedure
1.4 Removal of Outdoor Fan / Fan Motor
Procedure Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure Points
1
Remove the 2 screws
of the fan motor fixing
plate.
Preparation
Remove the outer panels
and plates.
Remove the electrical box.
2
Remove the fan motor
fixing plate.
When reassembling, fit the
lower hooks.
Nut size: M6
When reassembling, align
the mark of the outdoor
fan with the D-cut section of
the motor shaft.
3
Remove the nut and
remove the outdoor fan.
Fan motor fixing plate
(R12908)
(R5561)
(R5564)
10 mm
(R12236)
Outdoor fan
(R12909)
(R14592)
Nut
D-cut
mark

Table of Contents

Other manuals for Daikin FFQ35B9V1B