EasyManua.ls Logo

Daikin FFQ35B9V1B - Signal Transmission Error; (Between MAIN Remote Controller and SUB Remote Controller); Signal Transmission Error (between MAIN Remote Controller and SUB Remote Controller)

Daikin FFQ35B9V1B
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting for SA Indoor Unit - FCQG, FFQ, FHQ, FDBQ, FBQ Series SiBE121135
294 Service Diagnosis
6.9 Signal Transmission Error (between MAIN Remote
Controller and SUB Remote Controller)
Remote
Controller
Display
U8
Method of
Malfunction
Detection
In case of controlling with 2 remote controllers, check the system using micro-computer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Remote controller is set to “SUB” when using 1 remote controller
Connection of 2 sub remote controllers (when using 2 remote controllers)
Defective remote controller PCB
Troubleshooting
Is SS1
of remote
controller PCB set to
"SUB"?
Turn the power off and then
back on. If a malfunction occurs,
replace the remote controller
PCB.
Set one remote controller to
"MAIN"; turn the power supply
off once and then back on.
Set SS1 to "MAIN"; turn the
power supply off once and then
back on.
YES
NO
YES
NO NO
YES
(R15321)
Using 2 remote
controllers?
Is SS1 of both
remote controllers
set to "SUB"?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Other manuals for Daikin FFQ35B9V1B

Related product manuals