Indoor Unit SiBE121135
70 Printed Circuit Board Connector Wiring Diagram
2.13 FBQ35/50/60C8VEB
Connectors and
Other Parts
[A1P]: Control PCB
[A2P]: Fan PCB (for FBQ35/50C8VEB)
[A2P]: Fan PCB (for FBQ60C8VEB)
[A3P]: Capacitor PCB (FBQ60C8VEB only)
1) X15A Connector for float switch
2) X16A Connector for room temperature thermistor
3) X17A Connector for indoor heat exchanger thermistor
4) X18A Connector for liquid pipe thermistor
5) X25A Connector for drain pump motor
6) X27A Connector for terminal board (for inter-unit wiring)
7) X28A Connector for power supply wiring (option)
8) X30A Connector for terminal board (for wired remote controller)
9) X33A Connector for wiring adaptor PCB (option)
10) X35A Connector for group control adaptor (option)
11) X70A Connector for fan PCB
12) X85A Connector for multi zoning (option)
13) HAP LED for service monitor (green)
14) SS1 Selector switch for emergency
1) X3A Connector for control PCB
2) X6A Connector for reactor
3) X8A Connector for fan motor
4) X10A Connector for terminal board (power supply)
5) F2U Fuse (5 A, 250 V)
6) F4U Fuse (6.3 A, 250 V)
7) HAP LED for service monitor (green)
1) X1A, X2A Connector for fan motor
2) X3A Connector for control PCB
3) X6A Connector for reactor
4) X9A Connector for capacitor PCB
5) X10A Connector for terminal board (power supply)
6) F3U Fuse (6.3 A, 250 V)
7) HAP LED for service monitor (green)
Connector for X9A on fan PCB
3P217472-1