25
2.18 Rotation Regulating Functions
Upper limit rotation
Limit rotationCommand rotation
Starting rotation
∆T
Defrost*
Lower limit rotation
Target rotation
* Defrost control for heat pump model only
2.18.1 Starting Rotation
Starting Control
To avoid excessive oil discharge from compressor or to promote oil lubrication during startup.
Topreventliquidoodbacktothecompressor.
To limit starting current.
When compressor starts to rotate from OFF to ON, compressor rotation is set to run gradually to each upper
limitataspecictimersetting.
Model
a Hz
(Time, s)
b Hz
(Time, s)
c Hz
(Time, s)
d Hz
(Time, s)
Max Hz
(Time, s)
RK(X)B09/12AXVJU
RK(X)N09/12AXVJU
40 (180) 54 (420) 72 (180) 90 (120) -
RK(X)B18/24AXVJU
RK(X)N18/24AXVJU
55 (120) 70 (200) 85 (470) - -
2.18.2 Command Rotation
Cut in upon termination of Starting Control.
Achieve capacity control by controlling the compressor rotation based on:
• Temperaturedifferencebetweensetandroomtemperature,∆T.
• Limit Rotation.
• Defrost control.