SiENBE12-713 Instruction
System Configuration 211
FAULT DIAGNOSIS BY REMOTE CONTROL
In the ARC433A series, the temperature display sections on the main unit indicate corresponding codes.
1. When the TIMER CANCEL button is held down for 5 seconds, a “00” indication flashes on the temperature
display section.
2. Press the TIMER CANCEL button repeatedly until a continuous beep is produced.
The code indication changes as shown below, and notifies with a long beep.
NOTES
Fault dignosis.
CODE
MEANING
SYSTEM
00
NORMAL
UA
INDOOR-OUTDOOR UNIT COMBINATION FAULT
U2
DROP VOLTAGE OR MAIN CIRCUIT OVERVOLTAGE
U4 FAILURE OF TRANSMISSION (BETWEEN INDOOR UNIT AND
OUTDOOR UNIT)
INDOOR UNIT
A1 INDOOR PCB DEFECTIVENESS
A5 HIGH PRESSURE CONTROL OR FREEZE-UP PROTECTOR
A6 FAN MOTOR FAULT
C4 FAULTY HEAT EXCHANGER TEMPERATURE SENSOR
C9 FAULTY SUCTION AIR TEMPERATURE SENSOR
OUTDOOR UNIT
EA COOLING-HEATING SWITCHING ERROR
E1 CIRCUIT BOARD FAULT
E5 OL STARTED
E6 FAULTY COMPRESSOR START UP
E7 DC FAN MOTOR FAULT
E8 OVERCURRENT INPUT
F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL
F6 HIGH PRESSURE CONTROL (IN COOLING)
H0 SENSOR FAULT
H6 OPERATION HALT DUE TO FAULTY POSITION DETECTION SENSOR
H8 DC CURRENT SENSOR FAULT
H9 FAULTY SUCTION AIR TEMPERATURE SENSOR
J3 FAULTY DISCHARGE PIPE TEMPERATURE SENSOR
J6 FAULTY HEAT EXCHANGER TEMPERATURE SENSOR
L3 ELECTRICAL PARTS HEAT FAULT
L4 HIGH TEMPERATURE AT INVERTER CIRCUIT HEATSINK
L5 OUTPUT OVERCURRENT
P4 FAULTY INVERTER CIRCUIT HEATSINK TEMPERATURE SENSOR
1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To cancel the code display, hold the TIMER CANCEL button down for 5 seconds. The code
display also cancel itself if the button is not pressed for 1 minute.
TIMER CANCEL button
It cancels the timer setting.