SiENBE12-713 Outdoor Unit
Removal Procedure 295
8
Disconnect the
connector for overload
protector [S40].
9 Remove the OL wire
harness and the
compressor wire
harness together from
the partition plate.
10 Use long-nose pliers or
the like to pull out the
clamp.
" Detach the clamp.
" Just pull the push-mount
type out of position.
11
Disconnect the
connector for relay
harness of compressor.
Step
Procedure Points
Clamp
(R6423)
Clamp