Troubleshooting
Fault diagnosis by remote controller
•IntheARC452Aseries,thetemperaturedisplaysectionsonthemainunitindicate
correspondingcodes.
1. When is held down for
5 seconds, a “ ” indication ashes on the
temperature display section.
2. Press repeatedly until a continuous
beep is produced.
•Thecodeindicationchangesasshownbelow,andnotieswithalongbeep.
CODE
MEANING
SYSTEM
00
NORMAL
UA
INDOOR-OUTDOORUNITCOMBINATIONFAULT
U0
REFRIGERANTSHORTAGE
U2
DROPVOLTAGEORMAINCIRCUITOVERVOLTAGE
U4
FAILUREOFTRANSMISSION(BETWEENINDOORUNITANDOUTDOORUNIT)
INDOOR
UNIT
A1
INDOORPCBDEFECTIVENESS
A5
HIGHPRESSURECONTROLORFREEZE-UPPROTECTOR
A6
FANMOTORFAULT
C4
FAULTYHEATEXCHANGERTEMPERATURESENSOR
C9
FAULTYSUCTIONAIRTEMPERATURESENSOR
OUTDOOR
UNIT
EA
COOLING-HEATINGSWITCHINGERROR
E1
CIRCUITBOARDFAULT
E5
OLSTARTED
E6
FAULTYCOMPRESSORSTARTUP
E7
DCFANMOTORFAULT
E8
OVERCURRENTINPUT
F3
HIGHTEMPERATUREDISCHARGEPIPECONTROL
F6
HIGHPRESSURECONTROL(INCOOLING)
H0
SENSORFAULT
H6
OPERATIONHALTDUETOFAULTYPOSITIONDETECTIONSENSOR
H8
DCCURRENTSENSORFAULT
H9
FAULTYSUCTIONAIRTEMPERATURESENSOR
J3
FAULTYDISCHARGEPIPETEMPERATURESENSOR
J6
FAULTYHEATEXCHANGERTEMPERATURESENSOR
L3
ELECTRICALPARTSHEATFAULT
L4
HIGHTEMPERATUREATINVERTERCIRCUITHEATSINK
L5
OUTPUTOVERCURRENT
P4
FAULTYINVERTERCIRCUITHEATSINKTEMPERATURESENSOR
NOTE
• Ashortbeepand2consecutivebeepsindicatenon-correspondingcodes.
• Tocancelthecodedisplay,holdthe
downfor5seconds.Thecodedisplayalsocancelitselfifthebuttonisnotpressedfor