Main Functions Si18-201
92 Main Functions
1.1.23 Program Dry Operation
By the function of the microcomputer, program dry operation reduces the humidity keeping the
temperature in a minimum drop. Room temperature and air volume can not be controlled by
room temperature adjusting button and air volume adjusting button because they are controlled
automatically. When the program dry function starts, dry operation is provided, and then it
repeats 5 minute suspension and 4-minute dry operation alternately. When the room
temperature rises, it repeats the above process from the beginning.
★1 Dry operation activating (compressor on) temperature
★2 Room temperature difference between activation and suspension of dry operation
Note: 1. The program dry function is not operated when the room temperature is at 18°C or less.
2. In monitoring operation, fan rotates 5 seconds after the compressor starts its operation.
Room temperature at starting of
program dry operation
Program dry activating
temperature ★1
Differential ★2
Above 24°C
Room temperature at starting of
program dry operation
1.5 deg
18°C~24°C
Room temperature at starting of
program dry operation
1.0 deg
Below 18°C18°C1.0 deg
5 minutes
4 minutes
Differential
Activating temp.
Suspention temp.
(RL001)
Compressor
Indoor fan
Suspension Operation
5 seconds
L tapSuspension
(RL002)