1 | Troubleshooting
Service manual
14
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Possible cause: Faulty expansion valve.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.10 E7-00 – Outdoor unit: Malfunction of outdoor unit fan motor
Trigger Effect Reset
Fan does NOT start
15~30seconds after ON
signal.
It can occur that the error
code is triggered when
the fan motor is running
caused by a faulty
rotating sensor signal.
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the outdoor unit fan motor. See "2.9 Outdoor unit fan
motor"[492].
Possible cause: Faulty outdoor unit fan motor.
2 Perform a check of the main PCB. See "2.8Main PCB"[474].
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.11 E8-00 – Outdoor unit: Power input overvoltage
Trigger Effect Reset
Compressor running
current exceeds standard
value for 2.5seconds.
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Check the outdoor temperature. See "3.3External factors"[4136].
Possible cause: Outdoor temperature is out of operation range.
2 Perform a check of the compressor. See "2.2Compressor"[444].