5 Installation
Installation manual
12
(A)(F)TXP20~71L2V1B + FTXF20~71A2V1B
Daikin room air conditioner
3P512025-1C – 2018.01
NOTICE
Do NOT apply lubricating oil (refrigerant oil) to the drain
plug when inserting it. The drain plug may deteriorate and
cause drain leakage from the plug.
a
a 4mm hexagonal wrench
3 Insert the drain hose on the left side and do not forget to tighten
it with the fixing screw; otherwise water leakage may occur.
a
b
a
b
a Insulation fixing screw
b Drain hose
4 Attach the drain hose to the refrigerant pipes bottom side using
adhesive vinyl tape.
A
B
C
b
a
A Left-side piping
B Left-back piping
C Left-bottom piping
a Remove the pipe port cover here for left-side piping.
b Remove the pipe port cover here for left-bottom piping.
To check for water leaks
1 Remove the air filters.
2 Gradually pour approximately 1l of water in the drain pan, and
check for water leaks.
5.3 Connecting the refrigerant piping
DANGER: RISK OF BURNING
5.3.1 Guidelines when connecting the
refrigerant piping
Take the following guidelines into account when connecting pipes:
Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before
tightening firmly.
ALWAYS use 2 wrenches together when loosening a flare nut.
ALWAYS use a spanner and torque wrench together to tighten the
flare nut when connecting the piping. This to prevent nut cracking
and leaks.
a
b
c
d
a Torque wrench
b Spanner
c Piping union
d Flare nut
Piping size
(mm)
Tightening
torque (N•m)
Flare
dimensions (A)
(mm)
Flare shape
(mm)
Ø6.4 15~17 8.7~9.1
R=0.4~0.8
45°
±2
90°
±2
A
Ø9.5 33~39 12.8~13.2
Ø12.7 50~60 16.2~16.6
5.3.2 To connect the refrigerant piping to the
indoor unit
Pipe length. Keep refrigerant piping as short as possible.
Flare connections. Connect refrigerant piping to the unit using
flare connections.
Insulation. Insulate the refrigerant piping, interconnection cable
and drain hose on the indoor unit as follows:
c
a
b
f
d
g
e
a Gas pipe
b Gas pipe insulation
c Interconnection cable
d Liquid pipe
e Liquid pipe insulation
f Finishing tape
g Drain hose
NOTICE
Make sure to insulate all refrigerant piping. Any exposed
piping might cause condensation.
5.4 Connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION