EasyManua.ls Logo

Daikin FTXF20E5V1B - Specifications of Standard Wiring Components

Daikin FTXF20E5V1B
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 | Electrical installation
Installer reference guide
40
FTXF20~42E5V1B + ATXF20~42E5V1B
Daikin room air conditioner
4P519439-19U – 2022.09
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
Or
Stranded conductor wire
twisted to "solid-like"
connection
c b
c
aa
A
AA´
a Curled wire (single-core or twisted stranded
conductor wire)
b Screw
c Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2
M4 (earth)
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
8.1.4 Specifications of standard wiring components
Component
Power supply cable Voltage 220~240V
Phase 1~
Frequency 50Hz
Wire sizes Must comply with applicable
legislation
Interconnection cable Minimum cable section of
2.5mm² and applicable for
220~240V
Recommended field fuse 20A
Earth leakage circuit breaker Must comply with applicable
legislation