6 | Unit installation
Installer reference guide
30
FTXF20~42E5V1B + ATXF20~42E5V1B
Daikin room air conditioner
4P519439-19U – 2022.09
NOTICE
Do NOT use nippers to remove the pipe port cover, as this would damage the front
grille.
6.3.5 To provide drainage
Make sure condensation water can be evacuated properly. This involves:
General guidelines
Connecting the drain piping to the indoor unit
Checking for water leaks
General guidelines
Pipe length. Keep drain piping as short as possible.
Pipe size. If drain hose extension or embedded drain piping is required, use
appropriate parts that match the hose front end.
Ø16
Ø18
NOTICE
Install the drain hose with a downward slope.
Traps are NOT permitted.
Do NOT put the end of the hose in water.
Drain hose extension. To extend the drain hose, use a field supplied hose with
inner Ø16mm. Do NOT forget to use a heat insulation tube on the indoor section
of the extension hose.
a
a
b c
Ø16
Ø16
a Drain hose supplied with the indoor unit
b Heat insulation tube (field supply)
c Extension drain hose
Ridgid polyvinyl chloride pipe. When connecting a ridgid polyvinyl chloride pipe
(nominal Ø13mm) directly to the drain hose as with embedded piping work, use
a field supplied drain socket (nominal Ø13mm).
a b c
Ø18
a Drain hose supplied with the indoor unit
b Drain socket with nominal Ø13mm (field supply)
c Ridgid polyvinyl chloride pipe (field supply)