8 | Electrical installation
Installer reference guide
36
FTXP-M + FTXF-D + FTXF-A + ATXF-A
Daikin room air conditioner
4P513661-12L – 2021.07
Wire type Installation method
Single-core wire
c b
c
aa
A
AA´
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2
M4 (earth)
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
1-3
8.1.3 Specifications of standard wiring components
Component
Interconnection cable (indoor↔outdoor) 4-core cable 1.5mm²~2.5mm²
andapplicable for 220~240V
H05RN-F (60245 IEC 57)
8.2 To connect the electrical wiring to the indoor unit
Electrical work should be carried out in accordance with the installation manual
and the national electrical wiring rules or code of practice.
1 Set the indoor unit on the mounting plate hooks. Use the " " marks as a
guide.