English
■English 10
6. Drain piping
1)Connectthedrainhose,asdescribedright.
The drain hose should
be inclined downward.
No trap is permitted.
Do not put the end
of the hose in water.
2)Removetheairltersandpoursomewaterintothedrainpantocheckthewaterows
smoothly.
3)Ifdrainhoseextensionorembeddeddrainpipingisrequired,useappropriatepartsthatmatchthehosefrontend.
[Figureofhosefrontend]
ϕ18ϕ16
4)Whenextendingthedrainhose,useacommerciallyavailable
extensionhosewithaninnerdiameterof16mm.
Besuretothermallyinsulatetheindoorsectionoftheextension
hose.
ϕ16
Drain hose supplied
with the indoor unit
Indoor unit
drain hose
ϕ16
Extension drain hose
Heat insulation tube
(field supply)
5)Whenconnectingarigidpolyvinylchloridepipe
(nominaldiameter13mm)directlytothedrain
hoseattachedtotheindoorunitaswithembed-
dedpipingwork,useanycommerciallyavailable
drainsocket(nominaldiameter13mm)asajoint.
Commercially available drain
socket
(nominal diameter 13mm)
Commercially available rigid
polyvinyl chloride pipe
(nominal diameter 13mm)
Drain hose supplied
with the indoor unit
ϕ18
Refrigerant Piping Work
1. Flaring the pipe end
1)Cutthepipeendwithapipecutter.
2)Removeburrswiththecutsurfacefacingdownward
sothatthechipsdonotenterthepipe.
3)Putthearenutonthepipe.
4)Flarethepipe.
5)Checkthatthearingisproperlymade.
Set exactly at the position shown below.
A
Flaring
Die
A 0-0.5mm
Clutch-type
Flare tool for R410A
1.0-1.5mm
Clutch-type (Rigid-type)
1.5-2.0mm
Wing-nut type (Imperial-type)
Conventional flare tool
(Cut exactly at
right angles.)
Remove burrs.
Check
Flare’s inner
surface must
be flaw-free.
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
WARNING
•Donotusemineraloilonaredpart.
•Preventmineraloilfromgettingintothesystemasthiswouldreducethelifetimeoftheunits.
•Neverusepipingwhichhasbeenusedforpreviousinstallations.Onlyusepartswhicharedeliveredwiththeunit.
•DoneverinstalladriertothisR410Aunitinordertoguaranteeitslifetime.
•Thedryingmaterialmaydissolveanddamagethesystem.
•Incompletearingmaycauserefrigerantgasleakage.
01_EN_3P297034-1.indd 10 10/12/2011 11:37:07 AM