Electric Characteristics EDUS041129
24 Split Type Air Conditioners FTXS-L Series
10.Electric Characteristics
3D063167A
3D071271A
Indoor Unit Outdoor Unit
Power Supply COMP OFM IFM
Hz - Volts Voltage Range MCA MFA RHz RLA W FLA W FLA
FTXS30LVJU RKS30LVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
19.5 20 66
13.5
200
0.39
64
0.37
60 - 230 12.2 0.35 0.34
FTXS36LVJU RKS36LVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
19.5 20
84 18.9
200
0.39
64
0.37
60 - 230 90 18.4 0.35 0.34
FTXS30LVJU RXS30LVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
19.5 20 66
18.1
200
0.39
64
0.37
60 - 230 16.4 0.35 0.34
FTXS36LVJU RXS36LVJU
60 - 208
MAX. 60 Hz, 253 V
MIN. 60 Hz, 187 V
19.5 20
84 20.3
200
0.39
64
0.37
60 - 230 90 18.4 0.35 0.34
Symbols: Notes:
MCA : Min. circuit amps (A) 1. RLA is based on the following conditions.
Indoor temp. : 80°FDB / 67°FWB (26.7°CDB / 19.4°CWB)
Outdoor temp. : 95°FDB (35°CDB)
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
MFA : Max. fuse amps (A)
RHz : Rated operating frequency (Hz)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)