5
Application Information
Model: UAHMM
Operating Limits:
Thermal carrier : Water
Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 70°C (Heating)
Maximum water pressure : 16 bar
Air temperature : (as below)
Cooling Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
19.0 / 66.2 14.0 / 57.2
Maximum indoor
temperature
32.0 / 89.6 23.0 / 73.4
Heating Mode
Temperature Ts °C/°F Th °C/°F
Minimum indoor
temperature
15.0 / 59.0 -
Maximum indoor
temperature
27.0 / 80.6 -
Ts: Dry bulb temperature. Th: Wet bulb temperature.