32 FXAQ-PVJU
10.4 Electrical Wiring Work
All fi eld supplied parts and materials and electric works must conform to local codes.
Use copper wire only.
For electric wiring work, refer to also “WIRING DIAGRAM” attached to the unit.
For remote controller wiring details, refer to the installation manual attached to the remote controller.
All wiring must be performed by an authorized electrician.
This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the
terminal block wiring to the outdoor unit and BRANCHSELECTOR unit is properly matched. If wiring and piping
BETWEENTHEoutdoor unit and indoor unit are mismatched, the system may cause a malfunction.
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected
to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
Be sure to ground the air conditioner.
DANGER
Do not ground units to water pipes, telephone wires or lightning rods because incomplete grounding
could cause a severe shock hazard resulting in severe injury or death, and to gas pipes because a gas
leak could result in an explosion which could lead to severe injury or death.
ELECTRICAL CHARACTERISTICS7-2
Units Power supply Fan motor
Model Hz Volts Voltage range MCA MOP W FLA
FXAQ07PVJU
60 208/230
Max. 253
Min. 187
0.4 15 40 0.3
FXAQ09PVJU 0.4 15 40 0.3
FXAQ12PVJU 0.4 15 40 0.3
FXAQ18PVJU 0.5 15 43 0.4
FXAQ24PVJU 0.6 15 43 0.5
MCA: Minimum Circuit Amps (A);
W: Fan Motor Rated Output (W);
MOP: Maximum Overcurrent Protective Device (A)
FLA: Full Load Amps (A)