EDUS391100-F6 Test Run
FXAQ-PVJU 39
11. Test Run
Make sure the control box covers are closed on the indoor and outdoor units.
Refer to the installation manual of the outdoor unit.
The operation lamp of the remote controller will fl ash when a malfunction occurs. Check the malfunction
code on the liquid crystal display to identify the point of trouble. An explanation of malfunction codes and
the corresponding trouble is provided in the installation manual of the outdoor unit.
If any of the items in Table 5 are displayed, there may be a problem with the wiring or power, so check
the wiring again.
Table 5
Remote controller display Content
(under centralized
control) is lit up
There is a short circuit at the FORCED OFF terminals (T1, T2).
“U4” is lit up
“UH” is lit up
The power on the outdoor unit is off.
The outdoor unit has not been wired for power supply.
Incorrect wiring for the transmission wiring and/or FORCED
OFF wiring.
The transmission wiring is cut.
No display
The power on the indoor unit is off.
The indoor unit has not been wired for power supply.
Incorrect wiring for the remote controller wiring, the transmis-
sion wiring, and/or the FORCED OFF wiring.
The remote controller wiring is cut.
If “U3” is lit up, the malfunction code shows the test run has not been performed yet.