• Indoor Unit • Wall mounted unit • FXAQ-P
•VRV
®
Systems • Indoor Unit
2
1 Specifications
Indoor Unit VRV
®
Systems FXAQ-PWall mounte
Standard Accessories : Screws;
Standard Accessories : Clamps;
Standard Accessories : Insulation tape;
Standard Accessories : Paper pattern for installation;
Standard Accessories : Installation panel;
Standard Accessories : Installation and operation manual;
1-1 Technical Specifications FXAQ20P FXAQ25P FXAQ32P FXAQ40P FXAQ50P FXAQ63P
Cooling capacity
Nom. kW 2.2 (1) 2.8 (1) 3.6 (1) 4.5 (1) 5.6 (1) 7.1 (1)
Heating capacity
Nom. kW 2.5 (2) 3.2 (2) 4.0 (2) 5.0 (2) 6.3 (2) 8.0 (2)
Power input -
50Hz
Cooling Nom. kW 0.019 (1) 0.028 (1) 0.030 (1) 0.020 (1) 0.033 (1) 0.050 (1)
Heating Nom. kW 0.029 (2) 0.034 (2) 0.035 (2) 0.020 (2) 0.039 (2) 0.060 (2)
Casing Colour White (3.0Y8.5/0.5)
Dimensions Unit Height mm 290
Width mm 795 1,050
Depth mm 238
Weight Unit kg 11 14
Heat
exchanger
Rows Quantity 2
Fin pitch mm 1.4
Face area m² 0.161 0.213
Stages Quantity 14
Fan Type Cross flow fan
Air flow rate -
50Hz
Cooling High
m³/min
7.5 8 8.5 12 15 19
Low
m³/min
4.555.59 1214
Fan motor Model QCL9661M QCL9686M
Output High W 40 43
Drive Direct drive
Sound
pressure level
Cooling High dBA 35.0 36.0 37.0 39.0 42.0 46.0
Low dBA 29.0 34.0 36.0 39.0
Refrigerant Type R-410A
Control Electronic expansion valve
Piping
connections
Liquid Type Flare connection
OD mm 6.35 9.52
Gas Type Flare connection
OD mm 12.7 15.9
Drain VP13 (I.D. 13/O.D. 18)
Heat insulation Foamed polystyrene/polyethylene
Sound absorbing insulation Foamed polystyrene / polyethylene
Temperature control Microprocessor thermostat for cooling and heating
Air filter Washable resin net
Safety devices Item 01 Fuse