1 Specifications
Notes
(1) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m (horizontal)
(2) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m (horizontal)
(3) Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
(4) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(5) Maximum allowable voltage range variation between phases is 2%.
(6) MCA/MFA: MCA = 1.25 x FLA
(7) MFA ≤ 4 x FLA
(8) Next lower standard fuse rating minimum 16A
(9) Select wire size based on the value of MCA
(10) Use a circuit breaker instead of a fuse.
1-2 Electrical Specifications FXAQ20P FXAQ25P FXAQ32P FXAQ40P FXAQ50P FXAQ63P
Power supply Name V1
Phase 1~
Frequency Hz 50
Voltage V 220-240
Voltage range Min. % -10
Max. % 10
Current - 50Hz Minimum circuit amps (MCA) A 0.3 0.4 0.5 0.6
Maximum fuse amps (MFA) A 16
Full load
amps (FLA)
Total A 0.2 0.3 0.4 0.5