16 | Unit installation
Installer and user reference guide
54
FXDA10~63A2VEB
VRV system air conditioner
4P599621-1A – 2020.10
a Drain outlet for maintenance
b Refrigerant pipes
c Drain pipe connection
1 Push the drain hose as far as possible over the drain pipe connection.
2 Tighten the metal clamp until the screw head is less than 4 mm from the
metal clamp part.
3 Check for water leaks (see "To check for water leaks"[455]).
4 Wind the large sealing pad (= insulation) around the metal clamp and drain
hose, and fix it with tie wraps.
5 Connect the drain piping to the drain hose.
≤4 mm
A-A'
b
a
d
c
3
1
2~61
4
d
A
A'
A
A'
e
5
2
c
ba
a Drain pipe connection (attached to the unit)
b Drain hose (accessory)
c Metal clamp (accessory)
d Large sealing pad (accessory)
e Drain piping (field supply)
NOTICE
Do NOT remove the drain pipe plug. Water might leak out.
Use the drain outlet only to discharge the water before maintenance.
Insert and remove the drain plug gently. Excessive force may deform the drain
socket of the drain pan.
Pull out the plug.
Do NOT wiggle the plug up and down.
a
Push in the plug.
Set the plug and push it in using a Phillips screwdriver.