Installation EDUS39-600-F2_a
28 FXDQ-M
• Remote controller and transmission wiring
Pull the wires into the unit through the wiring through hole
and connect to the terminal block (6P).
Be sure to put PVC or vinyl-clad wire into the control box.
WIRING EXAMPLES
No. 1 system When using 1 remote controller for
1 indoor unit
No. 2 system For group control or use with 2 remote
controllers
No. 3 system When including BS unit
〈 Precautions when laying power supply wiring 〉
• Wiring of different thicknesses cannot be connected to the
power supply wiring terminal block. (Slack in the power
supply wiring may cause abnormal heat.)
• Use sleeve-insulated round crimp-style terminals for con-
nections to the power supply wiring terminal block. When
none are available, connect wires of the same diameter to
both sides, as shown in the following figure.
Follow the instructions below if the wiring gets very hot
due to slack in the power supply wiring.
•For wiring, use the designated power supply wiring and
connect firmly, then secure to prevent outside pressure
being exerted on the terminal board.
• Use the correct screwdriver for tightening the terminal screws.
If the blade of screwdriver is too small, the head of the screw
might be damaged, and the screw will not be properly tight-
ened.
• If the terminal screws are tightened too hard, screws might
be damaged.
• Refer to the following below for the tightening torq
ue of the
terminal screws.
Indoor unit A Indoor unit B
Most
downstream
Indoor unit
Power supply
single phase
60Hz 208-230V
Power supply
single phase
60Hz 208-230V
Power supply
single phase
60Hz 208-230V
Outdoor unit
FT
1
L1
1
1
1
PP
2
P
L2
1
2
P
T
F
2
F
P
F
1
2
2
2
P
1
L2
2
P
2
F
IN/D
1
OUT/D
1
P
F
2
F
1
P
L1
F
1 2
T
2
T
1
PP
21
F
2
L2
F
L1
12
TT
P
Remote controller Remote controller Remote controller
Fig. 16
L1 L2
(option) (option) (option)
L1 L2 L1 L2
Outdoor unit
Note) There is not need to set the indoor unit
address when using group control.
(It is automatically set when the power
is turned on.)
Indoor
unit A
Indoor unit B
Most down-
stream
indoor unit
For use with 2
remote controllers
Case of group control
L1L2
Fig. 17
Remote controller
Remote controller
Remote controller
1
P
2
P
1
P
2
P
1
P
2
P
1
PP
21
F
2
L2
F
L1
L2L1
12
F
F
1
2
F
F
1
2
TT
1
PP
21
F
2
F
12
TT
L2L1
1
PP
21
F
2
F
12
TT
IN/D
OUT/D
(option)
(option)
Power supply
single phase
60Hz 208-230V
Outdoor unit
BS unit
L1 L2
Indoor unit A
Remote controller
(option)
Fig. 18
F
F
1
2
F
F
12
F
F
1
2
F
F
12
IN/D
IN/D
OUT/D OUT/D
1
PP
21
F
2
L2
F
L1
12
TT
1
P
2
P
Power supply
single phase
60Hz 208-230V
Electric wire
Round crimp-style terminal
Insulation sleeve
Connect wires of
the same gauge to
both sides.
Do not connect
wires of the same
gauge to one side.
Do not connect
wires of different
gauges.