EDUS39-600-F2_a Installation
FXDQ-M 19
FOR THE FOLLOWING ITEMS, BE ESPECIALLY
CAREFUL DURING CONSTRUCTION, AND CHECK
THEM AGAIN AFTER INSTALLATION IS COM-
PLETED:
a. Items to be checked after completion of work
Also review the SAFETY CONSIDERATIONS.
b. Items to be checked at time of delivery
3. SELECTING INSTALLATION SITE
CAUTION
• When moving the unit while removing it from the packing
case, be sure to lift it by the four hanger brackets. Avoid put-
ting any pressure on other parts especially the refrigerant
piping.
• If you think the humidity inside the ceiling might exceed 86°F
and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that the
thickness is more than 1/2 in. and fits inside the ceiling open-
ing.
(1) Select an installation site where the following condi-
tions are fulfilled and that meets with your customer’s
approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor
unit weight.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and ser-
vice can be ensured. (Refer to Fig. 1)
• Where piping between indoor and outdoor units is pos-
sible within the allowable limit. Refer to the installation
manual for the outdoor unit.
• Select the *H dimension such that a downward slope of
at least 1/100 is ensured as indicated in Section 7.
DRAIN PIPING WORK.
• The maintenance space marked with an asterisk is
required when the installation box for adaptor PC board
(KRP1B101) sold separately is used.
[ PRECAUTION ]
• Install the indoor and outdoor units, power supply wiring
and connecting wires at least 3.3 feet away from tele-
visions or radios in order to prevent image interference
or noise. Depending on the radio waves, a distance of
3.3 feet may not be sufficient enough to eliminate the
noise.
• If installing the wireless kit in a room with electronic flu-
orescent lighting, the remote controller’s transmission
distance may be shortened. Indoor units should be
installed as far away from fluorescent lighting as possi-
ble.
DANGER
• Do not install unit in an area where flammable materials are
present due to the risk explosion resulting in serious injury
or death.
Items to be checked
If not properly done, what
is likely to occur
Check
Are the indoor and out-
door unit fixed firmly?
Units may drop, vibrate or
make noise.
Is the gas leak test fin-
ished?
Insufficient cooling.
Is the unit fully insulated? Condensate may drip.
Does drainage flow
smoothly?
Condensate may drip.
Does the power supply
voltage correspond to that
shown on the name
plate?
The unit may malfunction
or the components burn
out.
Are wiring and piping cor-
rect?
The unit may malfunction
or the components burn
out.
Is the unit safely
grounded?
Incomplete grounding may
result in electric shocks.
Is wiring size according to
specifications?
The unit may malfunction
or the components burn
out.
Is something blocking the
air outlet or inlet of either
the indoor or outdoor
units?
Insufficient cooling.
Are refrigerant piping
length and additional
refrigerant charge noted
down?
The refrigerant charge in
the system is not clear.
Items to be checked Check
Did you explain about operations while showing the
operation manual to your customer?
Did you hand the operation manual and warranty over to
your customer?
Did you explain about the way of maintaining and clean-
ing local procurements such as (air filter, air outlet and
suction grilles to your customer?
Did you hand manuals of local procurements (in case
equipped) over to your customer?
Control box
Maintenance
space
Maintenance
space
12
or more
*12 or
more
13/16 or more
100 or more
*
H=
9-1/2 or more
7-7/8
Ceiling
Floor surface
(length : in.)
Fig. 1