5 | About the system
Installer and user reference guide
27
FXFA20~125A2VEB
VRV system air conditioner
4P599624-1A – 2020.06
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + transmission cable
g Drain pipe
h Suction grille and air filter
5.2 Information requirements for fan coil units
Item Symbol Value Unit
Cooling capacity (sensible) P
rated,c
A kW
Cooling capacity (latent) P
rated,c
B kW
Heating capacity P
rated,h
C kW
Total electric power input P
elec
D kW
Sound power level (per speed setting, if
applicable)
L
WA
E dB
Contact details:
DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o. U Nové Hospody 1/1155, 301 00 Plzeň
Skvrňany, Czech Republic
A B C D E
FXFA20 1.5 0.7 2.5 0.038 49
FXFA25 2 0.8 3.2 0.038 49
FXFA32 2.5 1.1 4 0.038 49
FXFA40 3.1 1.4 5 0.038 51
FXFA50 3.8 1.8 6.3 0.053 51
FXFA63 4.8 2.3 8 0.061 53
FXFA80 6.1 2.9 10 0.092 55
FXFA100 7.7 3.5 12.5 0.115 60
FXFA125 9.7 4.3 16 0.186 61