EasyManua.ls Logo

Daikin FXFQ20BVEB - 7 Configuration; Field Setting

Daikin FXFQ20BVEB
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 | Configuration
Installer and user reference guide
39
FXFQ20~125BVEB
VRV system air conditioner
4P561452-1B – 2021.07
7 Configuration
7.1 Field setting
Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
Ceiling height
Design decoration panel (if applicable)
Air flow direction
Air volume when thermostat control is OFF
Time to clean air filter
Setting: Ceiling height
This setting must correspond with the actual distance to the floor, capacity class
and air flow directions.
For 3-way and 4-way air flows (which require an optional blocking pad kit), see
the installation manual of the optional blocking pad kit.
For all-round air flow, use the table below.
If the distance to the floor is (m) Then
(1)
FXFQ20~63 FXFQ80~125 M C1 C2
≤2.7 ≤3.2 13 (23) 0 01
2.7<x≤3.0 3.2<x≤3.6 02
3.0<x≤3.5 3.6<x≤4.2 03
Setting: Decoration panel type
When installing or changing the decoration panel type, ALWAYS check if the
correct values are set.
If the … decoration panel is used Then
(1)
M C1 C2
Standard or self-cleaning 13 (23) 15 01
Design 02
Setting: airflow direction
This setting must correspond with the actual used airflow directions. See the
installation manual of the optional blocking pad kit and the manual of the user
interface.
Default: 01 (= all-round air flow)
Example:
(1)
Field settings are defined as follows:
M: Mode number – First number: for group of units – Number between brackets: for individual unit
C1: First code number
C2: Second code number
: Default

Table of Contents

Other manuals for Daikin FXFQ20BVEB

Related product manuals