•VRV
®
Systems • Indoor Units
3
Indoor Units • CEILING MOUNTED CORNER CASSETTE • FXKQ-MAVE
1 Specifications
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature
: 35°CDB, equivalent refrigerant piping : 7.5m (horizontal)
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB,
6°CWB, equivalent refrigerant piping : 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Sound pressure levels are measured at 220V
1-2 ELECTRICAL SPECIFICATIONS (50HZ) FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
Power Supply Name VE
Phase 1~
Frequency Hz 50
Voltage V 220-240
Current Minimum circuit amps (MCA) A 0.3 0.3 0.3 0.5
Maximum fuse amps (MFA) A 15 15 15 15
Full load amps (FLA) A 0.2 0.2 0.2 0.4
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-3 ELECTRICAL SPECIFICATIONS (60HZ) FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE
Power Supply Name VE
Phase 1~
Frequency Hz 60
Voltage V 220
Current Minimum circuit amps (MCA) A 0.4 0.4 0.5 0.6
Maximum fuse amps (MFA) A 15 15 15 15
Full load amps (FLA) A 0.3 0.3 0.4 0.5
Voltage range Minimum V -10%
Maximum V +10%
Notes Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals
is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA is smaller than or equal to 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
1-1 TECHNICAL SPECIFICATIONS FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE