4 English
(3) Use suspension bolts for installation. Check whether
the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling
before installing the unit.
(Installation pitch is marked on the paper pattern for instal-
lation. Refer to it to check for points requiring reinforcing.)
4. PREPARATIONS BEFORE INSTALLATION
(1) Relation of ceiling opening to suspension bolt position
(2) Open a hole in the ceiling for installation. (Case of existing
ceiling)
• Use the paper pattern for installation which has been
adjusted to the dimensions of the ceiling opening.
• Open a hole in the ceiling for installation at the place the
unit is to be installed, and run refrigerant and drain piping,
remote controller cord, and outdoor/indoor transmission
wiring to the unit’s piping and wiring hole. (For wiring pro-
cedure, refer to “WIRING EXAMPLE AND HOW TO SET
THE REMOTE CONTROLLER.” For piping procedure,
refer to the attached installation manual of the outdoor
unit.)
• After opening a hole in the ceiling, reinforcement of the
ceiling frame, etc., may be required to maintain the level-
ness of the ceiling and to prevent vibration of the ceiling.
For details, consult with your builder and interior contrac-
tor.
(3) Install the suspension bolts.
(Use M8 size suspension bolts.)
Use anchors for existing ceilings and embedded inserts,
embedded anchors, etc., for newly built ceilings so that the
weight of the unit can be supported. Adjust the length of the
bolts to the ceiling before installing the unit.
5. INDOOR UNIT INSTALLATION
Installing optional accessories (except for the decoration
panel) before installing the indoor unit is easier.
As for the parts to be used for installation work, be sure to use
the provided accessories and specified parts designated by our
company.
(1) Install the unit temporarily.
• Fix the hanger bracket to the suspension bolt. Tighten
both upper and lower nuts firmly using washers.
(2) Using the attached positioning jig for installation, adjust the
height of the unit.
(3) Adjust the unit to the correct position based on “SELECT-
ING INSTALLATION SITE.” (1).
• The positioning jig for installation and paper pattern for
installation have been adjusted to the dimensions of the
ceiling opening. Be sure to establish thorough communi-
cation with those who are to do the ceiling work.
(4) Check the unit is horizontally level.
The unit is equipped with a built-in drain pump and
float switch. Level the four corners with a level or a
vinyl tube containing water.
(If the unit is tilted against condensate flow, the float switch
may malfunction and cause water to drip.)
Model A B C D
FXKQ25 · 32 · 40M(A)VE(9) 1110 1150 1200 1240
FXKQ63M(A)VE(9) 1310 1350 1400 1440
20 or more
(length: mm)
(Suction side)(Discharge side)
220
or more
1500
or more
D
C
B
A
800
760
710
350
Decoration
panel
Indoor unit
(length: mm)
Suspension
bolt (×4)
Ceiling
opening
Ceiling slab
<Set-up example>
Ceiling surface (length: mm)
Note) All the above parts are field supplied.
Anchor
Wing nut or turnbuckle
Suspension bolt
Approx.
100
Part to be procured
in the field
Tighten from above and
below (Double nut)
Washer (accessory)
Screws (×4)
Lower
surface
of ceiling
Positioning
jig for
installation 2
Positioning jig for installation 1
(accessory)
Positioning jig for
installation 2
(accessory)
Positioning jig for installation 1
(accessory)
(accessory)
Positioning jig for installation
fastening screw hole