EDUS39-900-F10 Installation
FXMQ-MF 27
ELECTRICAL CHARACTERISTICS
SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE
Notes:
1. Select the particular size of electrical wire for power supply wire in accordance with the standards of the given nation
and region.
2. Allowable length of transmission wire between indoor/outdoor units and between the indoor unit and the remote
controller is as follows.
(1) Outdoor unit – Indoor unit:
Max. 3280ft. (Total wiring length: 6560ft.)
(2) Indoor unit – Remote controller:
Max. 1640ft.
(3) Max. branches No. of branches :16
3. Up to 16 branches are possible for unit-to unit cabling. No branch is allowed after first branch. (Refer to Fig. 15)
Units Power supply Fan motor
Model Hz Volts Voltage range MCA MOP W FLA
FXMQ48MFVJU
60 208-230
Max. 253
Min. 187
2.1 15 380 1.7
FXMQ72MFVJU 3.6 15 380 2.9
FXMQ96MFVJU 4.1 15 380 3.3
MCA: Min. Circuit Amps (A); MOP: Max. Overcurrent Protection (A)
W: Fan Motor Rated Output (W); FLA: Full Load Amps (A)
Model
Power supply wire
Remote controller wire
Transmission wire
Breaker Size Wire Size
FXMQ48MFVJU
15A
Size must comply with local
codes.
2- conductor, stranded non-
shielded copper cable/PVC
or vinyl jacket
AWG
18-2
FXMQ72MFVJU
FXMQ96MFVJU
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2
Branch
Subbranching
Fig. 15