ESIE15-11A | Part 3. Field settings 4. Wired remote controller BRC1E51
Page 34 23/09/16
VRV4 indoor units
1e 0 "set temp mode changeover" visibility
in main menu
01 visible
02 hide from main menu
1 enable temperature display in °C or °F 01
not visible from factory locked to °C
02 visible visible in menu, choice between °C
and °F
2 "setback" - function 01 not available Setback is home leave function
02
available
3 selection set temperature in limit oper-
ation when power on/off
01 not keep
02
keep
4 timer setting: when centralized control
(similar to BRC1D528 setting 1b-5)
01
not visible to avoid conflict between timer inside
centralized remocon and BRC1E
02 visible
5 hour indication 01
not visible in menu default 24h is activated
02 visible in menu enduser can choose 24h or 12h dis-
play
6 count down timer 01 not visible in menu
02
visible in menu
A Offset for master remocon sensor 01 -3°C with this setting it's possible to modify
the readout by remocon of the ambi-
ent temperature
02 -2,5°C
03 -2°C
04 -1,5°C
05 -1°C
06 -0,5°C
07
0°C
08 +0,5°C
09 +1°C
B offset for slave remocon sensor 01 -3°C with this setting it's possible to modify
the readout of ambient temperature of
the secondary remocon
02 -2,5°C
03 -2°C
04 -1,5°C
05 -1°C
06 -0,5°C
07
0°C
08 +0,5°C
09 +1°C