ESIE15-11A | Part 3. Field settings 5. Wired remote controller BRC1E52
Page 40 23/09/16
VRV4 indoor units
1e 0 "set temp mode changeover" visibility
in main menu
01 visible
02 hide from main menu
1 enable temperature display in °C or °F 01
not visible in menu from factory locked to °C
02 visible in menu visible in menu, choice between °C
and °F
2 Setback function 01 not available
02 available for heating
03 available for cooling
04
available for heating &
cooling
4 timer setting: when centralized control
(similar to BRC1D528 setting 1b-5)
01
not visible to avoid conflict between timer inside
centralized remocon and BRC1E
02 visible
5 hour indication 01
not visible in menu default 24h is activated
02 visible in menu enduser can choose 24h or 12h dis-
play
6 count down timer 01 not visible in menu
02
visible in menu
9 Display of 'change-over' and 'central-
ised' symbols
01 not visible on remocon whether or not the 'arrows' symbol is
visible on the remocon
02
visible in remocon
10 Display of info on remocon when acti-
vating prohibited function which is
locked through centralised control
01 show key-symbol
02
show message
11 switching delay in automatic mode 01 15 min
02 30 min
03
60 min
04 90 min