ESIE15-11A | Part 3. Field settings 6. General indoor units
23/09/16 Page 45
VRV4 indoor units
14/
24
2 when to display cleaning requirement
on the remote control according to
number of operating hours
01 Display after 1.250h only for BYCQ
02 Display after 2.500h
03
Display after 5.000h
3 Display filter change on the remote
control according to number of operat-
ing hours
01
no display
02 display after 32.000h
03 display after 48.000h
04 display after 72.000h
4 Panel indicator (green) 01 On while in a/c operation &
filter cleaning operation
02 possible to turn on while in
filter cleaning operation
only
03
off while in a/c operation
and filter cleaning opera-
tion
04 On
8 auto cleaning program 01
choice between auto and
schedule
02 only schedule (auto not in
menu)
9 Dust amount setting 01
standard
02 dust amount big
15 /
25
0 Drainpump operation (for units
equipped with drainpump 13VDC)
01 stop for 5 minutes when
thermo off
02
stop permanently during
thermo off
Air cleaner 01
not equipped
02 equipped
1 Humidification during thermo off (heat-
ing)
01
Off
02 On
2 Direct duct connection (ex. Fresh air
connection) to indoor
01
none
02 equipped Fan must be operated from indoor unit
3 Drain pump operation if humidifier is
used (heating)
01
not equipped
02 equipped
4 Filter sign 01
by timer
02 by external input
9 Demand control 01
not equipped
02 equipped