8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Model
Capacity
indication
Indoorairtemp.
14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PAVE 20 1.9 1.9 2.1 2.0 2.2 1.9 2.2 1.8 2.2 1.8 2.3 1.7 2.3 1.7
FXSQ25PAVE 25 2.5 2.2 2.6 2.2 2.8 2.3 2.8 2.2 2.8 2.1 2.9 2.0 3.0 2.0
FXSQ32PAVE 32 3.2 2.6 3.4 2.7 3.5 2.8 3.6 2.7 3.6 2.6 3.7 2.5 3.8 2.5
FXSQ40PAVE 40 4.0 3.5 4.2 3.8 4.4 4.0 4.5 3.7 4.6 3.6 4.7 3.4 4.8 3.4
FXSQ50PAVE 50 4.9 4.2 5.3 4.6 5.5 4.7 5.6 4.3 5.7 4.2 5.8 4.1 5.9 3.9
FXSQ63PAVE 63 6.3 5.3 6.7 5.7 7.0 5.9 7.1 5.4 7.2 5.4 7.3 5.2 7.5 5.1
FXSQ80PAVE 80 7.9 6.3 8.5 6.8 8.8 7.1 9.0 6.5 9.1 6.4 9.3 6.2 9.5 6.0
FXSQ100PAVE 100 9.9 8.2 10.5 8.9 11.0 9.2 11.2 8.5 11.3 8.4 11.6 8.1 11.8 7.9
FXSQ125PAVE 125 12.3 9.9 13.2 10.7 13.8 10.9 14.0 10.1 14.2 10.0 14.5 9.7 14.8 9.3
FXSQ140PAVE 140 14.1 11.0 15.0 11.8 15.7 12.4 16.0 11.6 16.2 11.4 16.5 11.1 16.9 10.6
TC: Totalcapacity:kW
SHC: Sensibleheatcapacity:kW
Notes:
1.ThesecapacitytablesareforusewhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchasthe
selectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconrmthatthecorrectedcapacityoftheVRVsystem
satisestherequiredheatload.
2.
showsratedcondition.
8.2 Cooling Capacity for Te: 6°C
Model
Capacity
indication
Indoorairtemp.
14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PAVE 20 1.5 1.5 1.8 1.7 2.1 1.8 2.2 1.8 2.2 1.8 2.3 1.7 2.3 1.7
FXSQ25PAVE 25 1.9 1.8 2.3 1.9 2.6 2.1 2.8 2.2 2.8 2.1 2.9 2.0 3.0 2.0
FXSQ32PAVE 32 2.4 2.0 2.9 2.3 3.4 2.6 3.6 2.7 3.6 2.6 3.7 2.5 3.8 2.5
FXSQ40PAVE 40 3.0 2.8 3.6 3.2 4.2 3.6 4.5 3.7 4.6 3.6 4.7 3.4 4.8 3.4
FXSQ50PAVE 50 3.8 3.3 4.5 3.8 5.2 4.2 5.6 4.3 5.7 4.2 5.8 4.1 5.9 3.9
FXSQ63PAVE 63 4.8 4.2 5.7 4.8 6.6 5.3 7.1 5.4 7.2 5.4 7.4 5.2 7.5 5.1
FXSQ80PAVE 80 6.1 5.0 7.2 5.7 8.4 6.4 9.0 6.5 9.1 6.4 9.3 6.2 9.5 6.0
FXSQ100PAVE 100 7.6 6.5 9.0 7.5 10.5 8.4 11.2 8.5 11.3 8.4 11.6 8.1 11.9 7.9
FXSQ125PAVE 125 9.4 7.7 11.3 8.9 13.1 9.9 14.0 10.1 14.2 10.0 14.5 9.7 14.9 9.4
FXSQ140PAVE 140 10.8 8.8 12.9 10.1 15.0 11.3 16.0 11.6 16.2 11.4 16.6 11.1 17.0 10.7
TC: Totalcapacity:kW
SHC: Sensibleheatcapacity:kW
Notes:
1.ThesecapacitytablesareforusewhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchasthe
selectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconrmthatthecorrectedcapacityoftheVRVsystem
satisestherequiredheatload.
2.
showsratedcondition.