19
8.3 Cooling Capacity for Te: 9°C
ForVRVindoorunitsonlyatTe:9°C/mixedcombinationofVRVandresidentialindoorunits
Model
Capacity
indication
Indoorairtemp.
14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXSQ20PAVE 20 1.0 1.0 1.3 1.3 1.7 1.6 1.8 1.6 1.8 1.6 1.9 1.5 2.0 1.5
FXSQ25PAVE 25 1.3 1.3 1.7 1.6 2.0 1.8 2.3 1.9 2.3 1.8 2.5 1.8 2.6 1.8
FXSQ32PAVE 32 1.7 1.6 2.2 1.9 2.7 2.3 2.9 2.4 3.0 2.3 3.2 2.3 3.3 2.3
FXSQ40PAVE 40 2.1 2.1 2.6 2.6 3.3 3.1 3.6 3.2 3.8 3.2 4.0 3.0 4.2 3.1
FXSQ50PAVE 50 2.5 2.5 3.2 3.1 4.0 3.6 4.5 3.7 4.6 3.6 4.9 3.6 5.1 3.5
FXSQ63PAVE 63 3.3 3.3 4.1 4.0 5.1 4.5 5.7 4.7 5.9 4.7 6.2 4.6 6.5 4.6
FXSQ80PAVE 80 4.1 3.9 5.3 4.8 6.6 5.5 7.3 5.7 7.5 5.6 7.9 5.6 8.3 5.5
FXSQ100PAVE 100 5.3 5.2 6.7 6.3 8.3 7.3 9.1 7.5 9.3 7.4 9.9 7.3 10.4 7.2
FXSQ125PAVE 125 6.5 6.1 8.4 7.5 10.4 8.6 11.4 8.9 11.7 8.8 12.4 8.8 13.1 8.6
FXSQ140PAVE 140 7.5 7.1 9.6 8.6 12.0 9.9 13.0 10.2 13.5 10.1 14.3 10.1 15.0 9.8
TC: Totalcapacity:kW
SHC: Sensibleheatcapacity:kW
Notes:
1.ThesecapacitytablesareforusewhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchasthe
selectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconrmthatthecorrectedcapacityoftheVRVsystem
satisestherequiredheatload.
2.
showsratedcondition.
8.4 Heating Capacity
Model
Capacity
indication
Indoorairtemp.
16°CDB 18°CDB 20°CDB 21°CDB 22°CDB 24°CDB
kW kW kW kW kW kW
FXSQ20PAVE 20 2.6 2.6 2.5 2.4 2.3 2.2
FXSQ25PAVE 25 3.4 3.2 3.2 3.1 3.0 2.8
FXSQ32PAVE 32 4.2 4.2 4.0 3.9 3.7 3.5
FXSQ40PAVE 40 5.2 5.2 5.0 4.8 4.7 4.4
FXSQ50PAVE 50 6.6 6.6 6.3 6.1 5.9 5.5
FXSQ63PAVE 63 8.4 8.4 8.0 7.7 7.5 7.0
FXSQ80PAVE 80 10.5 10.5 10.0 9.7 9.4 8.7
FXSQ100PAVE 100 13.1 13.1 12.5 12.1 11.7 10.9
FXSQ125PAVE 125 16.8 16.8 16.0 15.5 15.0 13.9
FXSQ140PAVE 140 18.9 18.9 18.0 17.4 16.8 15.7
Notes:
1.ThesecapacitytablesareforusewhenselectingaVRVindoorunit.TheactualcapacityoftheVRVsystemdependsonfactorssuchasthe
selectedmodelofoutdoorunits,outdoorairtemperatureandpipinglength.PleaseconrmthatthecorrectedcapacityoftheVRVsystem
satisestherequiredheatload.
2.
showsratedcondition.