Fig. 21
• Connect the terminal as shown in Fig. 22.
• Do not carry out soldering finish when stranded wires are
used. (Otherwise, the loosening of wires may result in
abnormal heat radiation.)
Use wires the same in size
(if the air conditioner is
in simultaneous multi operation)
Fig. 22
(Abnormal heating may occur if the wirings are not tightened
securely.)
• Use the required wirings, connect them securely and fix
these wirings securely so that external force may not apply to
the terminals.
• Use a proper screw driver for tightening the terminal screws.
If an improper screw driver is used, it may damage the screw
head and a proper tightening cannot be car ried out.
• If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of
terminals.
Table 6
Tightening torque (N·m)
Terminal block for remote controller
and transmission wirings
0.88 ± 0.08
Terminal for power supply 1.47 ± 0.14
Earth terminal 1.47 ± 0.14
• Do not carry out soldering when stranded wirings
are used.
WARNING
• When wiring, form the wirings orderly so that the control box
lid can be securely fastened. If the control box lid is not in
place, the wirings may come out or be sandwiched by the
box and the lid and cause electric shocks or a fire.
(1) Remove the control box lid.
Screws
(2 points)
Fig. 23
FXSQ20PAVE
60 220
Max. 242
Min. 198
0.8 15 0.078
0.6
FXSQ25PAVE 0.8 15 0.078
0.6
FXSQ32PAVE 0.8 15 0.078
0.7
FXSQ40PAVE 1.4 15 0.130
1.2
FXSQ50PAVE 1.3 15 0.230
1.1
FXSQ63PAVE 1.8 15 0.230
1.4
FXSQ80PAVE 1.8 15 0.230
1.5
FXSQ100PAVE 2.5 15 0.300
2.0
FXSQ125PAVE 2.8 15 0.300
2.2
FXSQ140PAVE 3.1 15 0.350
2.5
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)
9-3 SPECIFICATION FOR FIELD SUPPLY FUSES
AND WIRING
Table 5
Model
Power supply wiring
Remote controller wiring
Transmission wiring
Field
fuses
Wiring Size Wiring Size
FXSQ20PAVE
16A
H05VV-U3G
NOTE 1)
2.5 mm
2
NOTE 3)
Vinyl cord
with sheath
or cable
(2 core)
NOTE 2)
0.75-
1.25 mm
2
FXSQ25PAVE
FXSQ32PAVE
FXSQ40PAVE
FXSQ50PAVE
FXSQ63PAVE
FXSQ80PAVE
FXSQ100PAVE
FXSQ125PAVE
FXSQ140PAVE
The lengths of remote controller wiring are as follows:
Remote controller wiring (indoor unit - remote controller) ....Max. 500 m
NOTE
1.
2.
3.
Shows only in case of protected piping. Use H07RN-F in
case of no protection. (Do not lighter than 60245 IEC 57.)
Vinyl cord with sheath or cable (Insulated thickness : 1 mm
or more)
This size is based on IEC 60335-1 (Table 11), and this size
must comply with local codes.