FXSQ-PAVE EDFMT391737
5
Model FXSQ50PAVE FXSQ63PAVE
Powersupply 1phase,220-240/220V,50/60Hz 1phase,220-240/220V,50/60Hz
1 3Coolingcapacity
kcal/h 4,800 6,100
Btu/h 19,100 24,200
kW 5.6 7.1
2 3Heatingcapacity
kcal/h 5,400 6,900
Btu/h 21,500 27,300
kW 6.3 8.0
7
Powerinput
Cooling
50Hz kW 0.075 0.106
60Hz kW 0.075 0.106
Heating
50Hz kW 0.070 0.101
60Hz kW 0.070 0.101
Casing/Colour Galvanizedsteelplate Galvanizedsteelplate
Dimensions:(H×W×D) mm 245×1,000×800 245×1,000×800
Fan
Model — —
Type Siroccofan Siroccofan
Motoroutput×
Numberofunits
W 230×1 230×1
Airowrate(H/M/L)
m³/min 17/14.5/11.5 21/17.5/14.5
l/s 283/242/192 350/292/242
cfm 600/512/406 741/618/512
Externalstatic
pressure
Pa Rated50(150-504) Rated50(150-504)
Drive Directdrive Directdrive
Temperaturecontrol
Microprocessorthermostatfor
coolingandheating
Microprocessorthermostatfor
coolingandheating
Airlter — 5 — 5
Piping
connections
Liquidpipes mm
φ6.4(Flareconnection) φ9.5(Flareconnection)
Gaspipes mm
φ12.7(Flareconnection) φ15.9(Flareconnection)
Drainpipe mm
VP25
(
Externaldia.32
)
Internaldia.25
VP25
(
Externaldia.32
)
Internaldia.25
Mass kg 35 35
6Soundpressurelevel(H/M/L) dB(A) 34/32/29 36/32/29
Soundpowerlevel(H) dB 62 64
Safetydevices Fuse,Fandriveroverloadprotector Fuse,Fandriveroverloadprotector
Refrigerantcontrol Electronicexpansionvalve Electronicexpansionvalve
Standardaccessories
Operationmanual,Installationmanual,Drain
hose,Sealingmaterial,Clamps,Washers,
Screws,Thermalinsulation,Hoseband,Air
dischargeange,Airsuctionange
Operationmanual,Installationmanual,Drain
hose,Sealingmaterial,Clamps,Washers,
Screws,Thermalinsulation,Hoseband,Air
dischargeange,Airsuctionange
DrawingNo.
Specication C:3D105249A C:3D105249A
Soundlevel C:4D095807B C:4D095808B
Notes:
1. Indoortemp.:27°CDB,19°CWB/outdoortemp.:35°CDB/Ratedexternalstaticpressure/Equivalentpiping
length:7.5m,leveldierence:0m.
2. Indoortemp.:20°CDB/outdoortemp.:7°CDB,6°CWB/Ratedexternalstaticpressure/Equivalentpipinglength:
7.5m,leveldierence:0m.
3. Capacitiesarenet,includingadeductionforcooling(anadditionforheating)forindoorfanmotorheat.
4. Externalstaticpressureischangeablein13stages(20-40class),11stages(50-125class),10stages(140class)
byremotecontroller.
5. Airlterisnotstandardaccessory,butpleasemountitintheductsystemofthesuctionside.Selectitsdust
collectioneciency(gravitymethod)50%ormore.
6. Anechoicchamberconversionvalue,measuredatapoint1.5mdownwardfromtheunitcentre.Duringactual
operation,thesevaluesarenormallysomewhathigherasaresultofambientconditions.
7. Powerinputvaluesarebasedonconditionsofratedexternalstaticpressure.
8. RefertoElectric Characteristicsforthepowerinputwhentheairowrateismaximumatmaximumexternal
staticpressure.
Conversionformulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
l/s=m³/min×1000/60