Setting up the interval for sequential start/stop
This function prevents all management points to be started or stopped at once when start/stop is
ordered for an area by sequentially starting or stopping its member management points and areas
in the order they are listed in the Area Member Registration screen.
(15)
(16)
1. Touch the Modify buttons (15) and (16) on the Area Attribute Setup screen. Enter the interval for
starting or stopping in the Numerical Input dialog box that appears. The range of values you can
specify is 0 to 180 seconds.
ON after 0 sec
ON after 2 sec
ON after 4 sec
ON after 6 sec
Area1
Starting interval: 2 sec
2-sec interval
2-sec interval
2-sec interval
···
Area
··· Management point