EasyManua.ls Logo

Daikin Intelligent Touch Manager DCM002A71 - Setting up the Emergency Stop

Daikin Intelligent Touch Manager DCM002A71
309 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
188
8-3 Setting up the Emergency Stop
The iTM includes the Emergency Stop as standard function (see page 107).
The Emergency Stop is a control function envisioned primarily as a measure against re. Based on
the emergency stop program, this function stops the management points set up as output when the
input signal set up as the emergency stop signal is received.
The Default program stops all D3 units registered as management point when an emergency stop
signal is received.
The Default program cannot be edited, except from toggling enable and disable.
If the optional Emergency Stop Control function is enabled, you can create your own emergency
stop program.
The following describes how to create and set up an emergency stop program.
1. Touch the Emergency Stop button on the Automatic Ctrl. tab of the Menu List screen and display
the Emergency Stop Control screen (see page 52).
(2)
(1)
(3)
(4)
(5)
(6)
2. (1) is the list of emergency stop programs. Perform the intended operation by touching the
relevant button on the right.
(2) Create button
Creates a new program. You can create up to 32 emergency stop programs (including the
Default program).
(3) Copy button
Copies the selected program for editing.
(4) Delete button
Deletes the selected program.

Table of Contents

Related product manuals