10.4.10 Emergency Stop Alarm
This alarm is generated any time the Emergency Stop button is activated.
Before resetting the Emergency Stop button please verify that the harmful condition has been removed.
Symptom
Cause
Unit status is Off.
All circuits are stopped immediately.
Bell icon is moving on controller’s
display. String in the alarm list:
UnitOffEmergencyStop String in the
alarm log:
UnitOffEmergencyStop
String in the alarm snapshot
UnitOffEmergencyStop
Emergency stop button has been
pushed.
Reset
Local HMI
Network
Auto
10.5 Unit Pumpdown Stop Alarms
The following unit pumpdown stop alarms. These alarms will not stop the unit immediately but with a normal shutdown
procedure.
10.5.1 Evaporator Entering Water Temperature Sensor Fault
This alarm is generated any time the input resistance is out of an acceptable range.
Symptom
Cause
Solution
Unit status is Off.
All circuits are stopped with a normal
shutdown procedure.
Bell icon is moving on controller’s
display. String in the alarm list:
UnitOffEvpEntWTempSen
String in the alarm log:
UnitOffEvpEntWTempSen
String in the alarm snapshot
UnitOffEvpEntWTempSen
Sensor is broken.
Check for sensor integrity. according
table and allowed kOhm (k) range.
Check correct sensors operation.
Sensor is shorted.
Check if sensor is shorted with a
resistance measurement.
Sensor is not properly connected
(open).
Check for absence of water or
humidity on electrical contacts.
Check for correct plug-in of the
electrical connectors.
Check for correct sensors wiring also
according electrical scheme.
Reset
Notes
Local HMI
Network

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals