DEOMWC00A07-16_02EN
64/77
Solid Green
Ready for Communication. (All Parameter loaded, Neuron configured). Doesn't
indicate a communication with other devices.
Solid Yellow
Startup
Solid Red
No Communication to Neuron (internal error, could be solved by downloading a new
LON application).
Flashing Yellow
Communication not possible to the Neuron. The Neuron must be configured and set
online over the LON Tool.
Bacnet MSTP:
BuS LED
Mode
Solid Green
Ready for Communication. The BACnet Server is started. It doesn't indicate a active
communication.
Solid Yellow
Startup
Solid Red
BACnet Server down. Automatically a restart after 3 seconds are initiated.
Bacnet IP:
BuS LED
Mode
Solid Green
Ready for Communication. The BACnet Server is started. It doesn't indicate a active
communication.
Solid Yellow
Startup. The LED stays yellow until the module receives a IP Address, therefore a link
must be established.
Solid Red
BACnet Server down. Automatic restart after 3 seconds is initiated.
Modbus
BuS LED
Mode
Solid Green
All Communication running.
Solid Yellow
Startup, or one configured channel not communicating to the Master.
Solid Red
All configured Communications down. Means no communication to the Master. The
timeout can be configured. In case that the timeout is zero the timeout is disabled.

Table of Contents

Other manuals for Daikin MicroTech I

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech I and is the answer not in the manual?

Daikin MicroTech I Specifications

General IconGeneral
BrandDaikin
ModelMicroTech I
CategoryController
LanguageEnglish

Related product manuals