www.DaikinApplied.com 33 IM 1285-4 • MICROTECH III
Table 5: ACH580 Parameters
MD5 Parameters
# Name Unit VALUE
GROUP 96 - SYSTEM
96.04 MACRO SELECT
HVAC DEFAULT
GROUP 99 - MOTOR DATA
99.06 MOTOR NOM CURR A Motor Specific
99.07 MOTOR NOM VOLT V
Motor Specific
99.09 MOTOR NOM SPEED RPM
Motor Specific
99.10 MOTOR NOM POWER HP
Motor Specific
GROUP 12 - STANDARD AI
12.15 AI1 UNIT SELECTION MA
12.19 AI1 SCALED ATAI1 MIN 200
12.20 AI1 SCALED AT AI1 MAX 1000
12.25 AI2 UNIT SELECTION MA
12.29 AI2 SCALED AT AI2 MIN 200
12.30 AI2 SCALED AT AI2 MAX 1000
GROUP 20 - START/STOP/DIR
20.01 EXT1 COMMANDS EMBEDDED FIELDBUS
20.21 DIRECTION FORWARD
20.41 START INTERLOCK 1 NOT USED
20.42 START INTERLOCK 2 NOT USED
GROUP 22 - REFERENCE SELECT
22.11 EXT SPEED REF1 EFB REF1
22.22 CONSTANT SPEED SEL1 ALWAYS OFF
22.41 SPEED REF SAFE RPM 0
GROUP 28 - FREQUENCY REFERENCE CHAIN
28.11 EXT1 FREQUENCY REF1 EFB REF1
28.22 CONSTANT FREQ SEL1 ALWAYS OFF
28.41 FREQUENCY REF SAFE Hz 0
28.72 FREQ ACCELERATION TIME 1 S 60
28.73 FREQ DECELERATION TIME 1 S 60
GROUP 31 - FAULT FUNCTIONS
31.01 External Event 1 Source DI2
31.14 NUMBER OF TRIALS 5
31.16 DELAY TIME S 3
31.27 STALL FREQUENCY LIMIT Hz 45
31.25 AR OVERCURRENT ENABLE
GROUP 46 - MONITOR / SCALING SETTINGS
46.02 FREQUENCY SCALING 1000
GROUP 58 - EMBEDDED FILEDBUS
58.01 PROTOCOL ENABLE MODBUS RTU
58.03 NODE ADDRESS
1 (SAF) or 2 (RF/EF)
58.04 BAUD RATE
19.2 KBPS
58.05 PARITY 8 NONE 2
58.14 COMMUNICATION LOSS ACTION SPEED REF SAFE
58.15 COMMUNICATION LOSS MODE CW/REF1/REF2
58.16 COMMUNICATION LOSS TIME S 25.0 S
58.33 ADDRESSING MODE MODE0
GROUP 71 - EXTERNAL PID1
71.32 GAIN 1.00
71.33 INTEGRATION TIME S 2155
GROUP 97 - MOTOR CONTROL
97.20 U/F RATIO LINEAR
58.06 Communication Control
Enabled