www.DaikinApplied.com 35 IM 1285-4 • MICROTECH III
Figure 30: ATV 212 (MD2) Drive Parameters
PART NUMBER REV
PART DESCRIPTION
170632000
B Rooftop - MT3 SAF (set 321) PARAMETERS
Drive Voltage HP Application
ATV21 ALL ALL
SAF/RAF, RT/SC
Code Function Description Unit Min. Value Max. Value
Default
Value
New Value
Logical
Address
AU1
Automatic acceleration/deceleration
1021 0
0
AU4
Automatic function setting
1040 1
40
CMOd
Command mode selection
1020 2
3
FMOd
Frequency setting mode selection 1
1151 4
4
FMSL
Meter selection
1 0 19 0
5
FM
Meter adjustment
1 1 1280 145 318
6
tyP
Default setting
1090
7
Fr
Forward/reverse run selection (Operation panel)
1030
8
ACC
Acceleration time 1
0.1sec 0,0 3200,0 10 60
9
DEC
Deceleration time 1
0.1sec 0,0 3200,0 10 60
10
FH
Maximum frequency
0.01Hz 30,00 200,00 50 60
11
UL
Upper limit frequency
0.01Hz 0,50 80,00 50 60
12
LL
Lower limit frequency
0.01Hz 0,00 60,00 0 20
13
vL
Base frequency 1
0.01Hz 25,00 200,00 50 60
14
vLv
Base frequency voltage 1
0.1V 50,0 660,0
McQuay load 409
Pt
V/F control mode selection 1
1061
15
vb
Torque boost 1
0.10% 0,0 30,0 5
16
tHr
Motor electronic-thermal protection level 1
1% 10 100 100
600
OLM
Electric-thermal protection characteristic selection
1070 1
17
Sr1
Preset-speed operation frequency 1
0.01Hz 0,00 60,00 15
18
Sr2
Preset-speed operation frequency 2
0.01Hz 0,00 60,00 20
19
Sr3
Preset-speed operation frequency 3
0.01Hz 0,00 60,00 25
20
Sr4
Preset-speed operation frequency 4
0.01Hz 0,00 60,00 30
21
Sr5
Preset-speed operation frequency 5
0.01Hz 0,00 60,00 35
22
Sr6
Preset-speed operation frequency 6
0.01Hz 0,00 60,00 40
23
Sr7
Preset-speed operation frequency 7
0.01Hz 0,00 60,00 45
24
F100
Low-speed signal output frequency
0.01Hz 0,00 80,00 0
100
F101
Speed reach setting frequency
0.01Hz 0,00 80,00 0
101
F102
Speed reach detection band
0.01Hz 0,00 80,00 2.5
102
F108
2nd always-active function selection
1 0 71 0
108
F109
Analog/contact input function selection (VIA/VIB)
1020
109
F110
Always-active function selection
1 0 71 1
110
F111
Input terminal selection1 (F)
1 0 71 2 45
111
F112
Input terminal selection 2 (R)
1 0 71 6 0
112
F113
Input terminal selection 3 (RST)
1 0 71 10
113
F118
Input terminal selection 8 (VIA)
1 0 71 7
118
F130
Output terminal selection 1A (RY-RC)
1 0 255 4 14
130
F132
Output terminal selection 3 (FL)
1 0 255 11
132
F137
Output terminal selection 1B (RY-RC)
1 0 255 255
137
F139
Output terminal logic selection (RY-RC/OUT-NO)
1010
139
F167
Frequency command agreement detection range
0.01Hz 0,00 80,00 2.5
167
F170
Base frequency 2
0.01Hz 25,00 200,00 50 60
170
F171
Base frequency voltage 2
0.1V 50,0 660,0
171
F172
Torque boost 2
0.10% 0,0 30,0 5
172
F173
Motor electronic-thermal protection level 2
1% 10 100 100
173
F185
Stall prevention level 2
1% 10 111 110
185
F200
Frequency priority selection
1010
200
F201
VIA input point 1 setting
1% 0 100 0
201
F202
VIA input point 1 frequency
0.01Hz 0,00 200,00 0
202
F203
VIA input point 2 setting
1% 0 100 100
203
F204
VIA input point 2 frequency
0.01Hz 0,00 200,00 50
204