IM 1285-4 • MICROTECH III 37 www.DaikinApplied.com

Figure 30 continued: ATV 212 (MD2) Drive Parameters
PART NUMBER REV
PART DESCRIPTION
170632000
B Rooftop - MT3 SAF (set 321) PARAMETERS
Drive Voltage HP Application
ATV21 ALL ALL
SAF/RAF, RT/SC
Code Function Description Unit Min. Value Max. Value
Default
Value
New Value
Logical
Address
F471 VIA gain
1 0 255 148
471
F472 VIB bias
1 0 255 128
472
F473 VIB gain
1 0 255 148
473
F480 Exciting strengthening coefficient
1% 100 130 100
480
F481 Factory adjustment 1
1 0 9999 0
481
F482 Factory adjustment2
1 0 9999 442
482
F483 Factory adjustment3
0.1 0,0 300,0 100
483
F485 Stall cooperation gain at field weakening zone 1
1 10 250 100
485
F492 Stall cooperation gain at field weakening zone 2
1 50 150 100
492
F494 Motor adjustment factor
1 0 200 70
494
F495 Maximum voltage adjustment factor
1% 90 120 104
495
F496 Carrier change adjustment factor
0.1kHz 0,1 14,0 14
496
F500 Acceleration time 2
0.1sec 0,0 3200,0 20
500
F501 Deceleration time 2
0.1sec 0,0 3200,0 20
501
F502 Acceleration/deceleration 1 pattern
1020
502
F503 Acceleration/deceleration 2 pattern
1020
503
F504 Acceleration/deceleration selection (1/2/3)
1121
504
F505 Acceleration/deceleration 1 and 2 switching frequency
0.01Hz 0,00 60,00 0
505
F506 S-pattern lower-limit adjustment amount
1% 0 50 10
506
F507 S-pattern upper-limit adjustment amount
1% 0 50 10
507
F601 Stall prevention level 1
1% 10 111 110
601
F602 Inverter trip retention selection
1010
602
F603 Emergency stop selection
1020
603
F604 Emergency DC braking time
0.1sec 0,0 20,0 1
604
F605 Output phase failure detection mode selection
10535
605
F607 Motor 150%-overload time limit
1sec 10 2400 300
607
F608 Input phase failure detection mode selection
1011
608
F609 Hysteresis for small current detection
1% 1 20 10
609
F610 Low current trip/alarm
1010
610
F611 Small current detection current
1% 0 100 0
611
F612 Small current detection time
1sec 0 255 0
612
F613 Detection of output short-circuit during start-up
1030
613
F615 Over-torque trip/alarm selection
1010
615
F616 Over-torque detection level
1% 0 250 130
616
F618 Over-torque detection time
0.1sec 0,0 10,0 0.5
618
F619 Over-torque detection level hysteresis
1% 0 100 10
619
F621 Cumulative operation time alarm setting
0.1 0,0 999,9 610
621
F626 Over-voltage stall protection level
1% 100 150 140
626
F627 Under-voltage trip/alarm selection
1020
627
F632 Thermal memory selection
1010
632
F633 Trip at VIA low level input mode
1% 0 100 0
633
F634 Annual avg ambient temp (calculation for life alarms)
1163
634
F645 Selection of PTC thermal
1020
645
F646 Detection level of PTC
1ohm 100 9999 3000
646
F650 Rorced/Fire-speed control selection
1010
650
F691 Inclination characteristic of analog output
1011
691
F692 Meter bias
1% 0 100 0
692
F700 Prohibition of change of parameter settings
1010
700
F701 Unit selection
1011
701
F702 Free unit selection
0.01 0,00 200,00 0
702
F705 Inclination characteristic of free unit display
1011
705
ATV21 MT3 SAF PAGE 3