10.8.5 High Discharge Temperature
This alarm indicates that the temperature at the discharge port of the compressor exceeded a maximum limit which may
cause damages to the mechanical parts of the compressor.
When this alarm occurs compressor’s crankcase and discharge pipes may become very hot. Be
careful when getting in contact with the compressor and discharge pipes in this condition.
10.8.6 High Oil Pressure Difference
This alarm indicates that the oil filter is clogged and needs to be replaced.
Symptom
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 OffOilPrDiffHi
String in the alarm log:
CxCmp1 OffOilPrDiffHi
String in the alarm snapshot
CxCmp1 OffOilPrDiffHi
Reset
Local HMI
Network
Auto