DEOMWC00A07-16_02EN
56/77
10.8.15 Condenser Pressure Sensor Fault
This alarm indicates that the condensing pressure transducer is not operating properly.
Symptom
Cause
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 CondPressSen
String in the alarm log:
CxCmp1 CondPressSen
String in the alarm snapshot
CxCmp1 CondPressSen
Sensor is broken.
Sensor is shorted.
Sensor is not properly connected
(open).
Reset
Local HMI
Network
Auto
10.8.16 Motor Temperature Sensor Fault
This alarm is generated to indicate that the sensor is not reading properly.
Symptom
Cause
Circuit status is Off.
The circuit is switched off with the
normal shutdown procedure.
Bell icon is moving on controller’s
display.
String in the alarm list:
CxCmp1 OffMtrTempSen
String in the alarm log:
CxCmp1 OffMtrTempSen
String in the alarm snapshot
CxCmp1 OffMtrTempSen
Sensor is shorted.
Sensor is broken.
Sensor is not good connected (open).
Reset
Local HMI
Network
Auto