OM 1085-6 • MICROTECH III CONTROLLER 30 www.DaikinApplied.com


SmartSource Compact
I/O Expansion Module Option Hardware Jumpers Setting Description
Fan Row Selection (V6.2 & Newer) JP1 & JP2
Fan row selection for the: FanOnly, Hydronic Heating, and Hydronic Cooling
machine states.
Secondary Heating JP3 & JP4
JP3 = Open
None
JP4 = Open
JP3 = Shorted
Supplemental Electric Heat
JP4 = Open
JP3 = Open
Boilerless Electric Heat
JP4 = Shorted
JP3 = Shorted
Hydronic Heating (v6.0 & Newer)
JP4 = Shorted
 JP5 & JP6
JP5 = Open
None
JP6 = Open
JP5 = Shorted

JP6 = Open
JP5 = Open
Hydronic Cooling (Waterside Economizer)
JP6 = Shorted
Not Used JP7 JP7 = Open
Compressor Capacity JP8
JP8 = Open Single Stage Compressor
JP8 = Shorted Dual Stage Compressor

Compact
3
Model
Number
Compressor

Supplemental
Electric Heat
Boilerless
Electric Heat

Heat
2
HGR
Waterside
Economizer
1
1
Single Stage
2 Single Stage X
3 Single Stage X
4 Single Stage X
5 Single Stage X X
6 Single Stage X X
7 Single Stage X
8 Single Stage X X
9 Single Stage X X
10 Single Stage X
11 Single Stage X X
12 Single Stage X X
13 Two Stage
14 Two Stage X
15 Two Stage X
16 Two Stage X
17 Two Stage X X
18 Two Stage X X
19 Two Stage X
20 Two Stage X X
21 Two Stage X X
22 Two Stage X
23 Two Stage X X
24 Two Stage X X
1
Except for SmartSource Two Stage Compressor (Series2) WSHP with a single speed fan with no options selected, all other SmartSource Two Stage Compressor
(Series2) WSHPs require both the unit controller and I/O expansion module.
2
Hydronic heating is only available for unit controller software v6.0 and newer.
3
An “X” means that option is available for the corresponding WSHP model.

Other manuals for Daikin MicroTech III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin MicroTech III and is the answer not in the manual?

Daikin MicroTech III Specifications

General IconGeneral
BrandDaikin
ModelMicroTech III
CategoryController
LanguageEnglish

Related product manuals